What is the EPA SPCC rule under Clean Water Act Section 311?
The Spill Prevention, Control, and Countermeasure (SPCC) rule (40 CFR Part 112) helps facilities prevent discharges of oil into navigable waters or adjoining shorelines. It applies to non-transportation-related commercial facilities storing oil that could reasonably be expected to discharge oil in harmful quantities.
What are the storage capacity thresholds triggering SPCC plan requirements?
A facility is subject to SPCC if it has: (1) a total aggregate aboveground oil storage capacity exceeding 1,320 U.S. gallons (only containers of 55 gallons or greater count), OR (2) a total completely buried underground oil storage capacity exceeding 42,000 U.S. gallons.
What qualifies a facility as a Tier I or Tier II Qualified Facility?
A facility is a Qualified Facility if it has 10,000 gallons or less in total aggregate aboveground oil storage capacity and has a clean spill history (no single discharge > 1,000 gal or two discharges > 42 gal within 3 years). Tier I facilities have no individual aboveground container > 5,000 gallons and can complete the EPA self-certification template. Tier II facilities have an individual container > 5,000 gallons and can self-certify a full plan without a PE.
When is a Professional Engineer (PE) certification mandatory for an SPCC plan?
A registered Professional Engineer (PE) must review and certify the SPCC plan if the facility's aggregate aboveground storage capacity exceeds 10,000 gallons, or if a qualified facility fails the clean spill history test, or if environmental equivalence or impracticability determinations are used.