EPA SPCC Rule Oil Storage Capacity & Plan Tier Auditor | 40 CFR Part 112

Audit EPA Spill Prevention, Control, and Countermeasure (SPCC) compliance (40 CFR Part 112): 1,320-gallon threshold, Tier I/II Qualified Facility self-certification vs PE certification.

SPCC Rule Applicability
-
Plan Classification
-
Certification Required
-

Statutory Provisions & Frequently Asked Questions

What storage capacities trigger the EPA SPCC rule under 40 CFR Part 112?

A facility is subject to the SPCC rule if: (1) It stores, transfers, uses, or consumes oil; (2) Could reasonably be expected to discharge oil into navigable waters or adjoining shorelines; and (3) Has aggregate aboveground oil storage capacity exceeding 1,320 US gallons (counting only containers with a capacity of 55 gallons or greater), or completely buried storage capacity exceeding 42,000 US gallons.

What is the difference between a Tier I and Tier II Qualified Facility?

Under 40 CFR § 112.3(g), a qualified facility has 10,000 gallons or less of total AST storage and a clean spill history. A Tier I facility has no individual container larger than 5,000 gallons and can complete the EPA's simplified Appendix G template. A Tier II facility has an individual container exceeding 5,000 gallons; it may prepare a self-certified plan, but cannot use the simplified template.

When is a Professional Engineer (PE) certification mandatory for an SPCC plan?

A licensed Professional Engineer must review and certify an SPCC plan whenever: (1) Total aboveground oil storage capacity exceeds 10,000 gallons; (2) The facility has a disqualifying spill history; or (3) The facility employs environmental equivalence determinations or impracticable secondary containment provisions.