Frequently Asked Questions (EPA LCRI Final Rule)
What is the new lead action level under the EPA LCRI final rule?
Under the EPA Lead and Copper Rule Improvements (LCRI) finalized in October 2024, the lead action level is lowered from 15 parts per billion (ppb or 0.015 mg/L) to 10 parts per billion (ppb or 0.010 mg/L). Exceeding this 90th percentile threshold mandates corrosion control treatment and public notification.
What is the mandatory service line replacement timeline under LCRI?
Under 40 CFR Part 141 Subpart I, water systems must replace 100 percent of lead service lines (LSLs) and galvanized service lines requiring replacement within 10 years of the compliance date, requiring a mandatory minimum rolling average replacement rate of at least 10 percent per year.
What updated tap sampling protocol does the LCRI require for lead service lines?
The LCRI requires water systems with lead service lines to collect both first-liter samples (reflecting interior building plumbing) and fifth-liter samples (reflecting water that has sat in the lead service line itself), utilizing whichever concentration is higher to calculate the 90th percentile compliance level.
What are the 24-hour public education requirements under LCRI?
If a water system exceeds the 10 ppb lead action level, it must issue a system-wide public notification within 24 hours to all consumers, and provide certified lead test results to individual households sampled within 3 business days.