EPA SPCC 40 CFR Part 112 Auditor

Oil Spill Prevention, Qualified Facility Tiers & Secondary Containment Engine

Storage & Facility Parameters

Count all containers ≥ 55 gallons (drums, bulk tanks, transformers, totes).
If > 5,000 gallons, Tier I self-certification is prohibited.
Standard requirement: 110% of largest container (includes 25-yr storm freeboard).

SPCC Regulatory Verdict & Tier Classification

Auditing...

Analyzing 40 CFR Part 112...

SPCC Rule Threshold Status (>1,320 Gal): --
Facility SPCC Tier Classification: --
Mandatory Secondary Containment Minimum: 0 Gal (110%)
Containment Adequacy Status: --
Professional Engineer (PE) Mandate: --
EPA Clean Water Act § 311 Daily Exposure: $0.00 / Day
40 CFR § 112 Secondary Containment Rule:
Required Containment = Largest Tank Volume × 110% (Freeboard Allowance)
Tier I Eligibility: Total Storage ≤ 10,000 Gal AND Largest Tank ≤ 5,000 Gal AND Clean Spill History
Non-compliance exposes facility to CWA § 311 penalties up to $64,618 per day!

Environmental Deficiencies & Spill Prevention Scorecard

Clean Water Act Section 311: Oil Pollution Prevention Enforcement

Under Clean Water Act Section 311 (33 U.S.C. § 1321) and 40 CFR Part 112, the EPA strictly regulates non-transportation facilities that handle, store, refine, or consume oil. The regulation applies broadly to any oil product, including mineral oil in electrical transformers, diesel generators, hydraulic oil reservoirs, and used cooking oil.

The 55-Gallon Container Aggregation Rule: When calculating whether a facility exceeds the 1,320-gallon threshold, only containers with a capacity of 55 US gallons or greater are counted. For instance, twenty-five 55-gallon drums equal 1,375 gallons, triggering full SPCC mandates even without any large fixed bulk tanks on site.

The STI SP001 Testing Standard: Under 40 CFR § 112.8(c)(6), visual inspections alone are insufficient for field-constructed or shop-built bulk storage tanks over time. Facilities must adopt formal industry standards, such as the Steel Tank Institute (STI) SP001 Standard for the Inspection of Aboveground Storage Tanks, incorporating periodic ultrasonic thickness testing.

Frequently Asked Questions (EPA 40 CFR 112)

Are oil-filled electrical transformers covered under SPCC?
Yes! Oil-filled operational equipment (such as electrical transformers, circuit breakers, and hydraulic power units) containing 55 gallons or more are counted toward the 1,320-gallon threshold. However, under 40 CFR § 112.7(k), operational equipment is eligible for an alternative compliance pathway allowing an oil spill contingency plan in lieu of sized secondary containment.
What constitutes 'navigable waters' for SPCC discharge risk?
The EPA interprets discharge potential extremely broadly. A facility has discharge potential if oil could enter storm sewers, ditches, gullies, municipal drainage culverts, or dry creek beds that eventually connect to streams, lakes, or rivers. Only facilities completely sealed in interior bomb-shelter environments without external drainage can claim zero discharge potential.
Can an owner write and certify their own SPCC Plan?
Yes, but ONLY if the facility qualifies as a Tier I or Tier II Qualified Facility (10,000 gallons or less of storage and clean spill history). Facilities with more than 10,000 gallons cannot self-certify under any circumstance; the plan must be stamped by a licensed Professional Engineer.
What are the spill reporting requirements under 40 CFR § 110?
Any discharge of oil that causes a sheen, discoloration, sludge, or emulsion on water or shoreline must be reported immediately to the National Response Center (NRC) at 1-800-424-8802. Furthermore, discharges over 1,000 gallons or two discharges over 42 gallons in a 12-month period require a formal written report to the EPA Regional Administrator within 60 days.