EPA Clean Water Act SPCC 40 CFR Part 112 Auditor

1,320-Gallon Threshold, Tier I/II Self-Certification & PE Mandate Engine
40 CFR Part 112 1,320 Gallon Aboveground Threshold Tier I Appendix G Template Max $59,973 / Day Fine

1. Oil Storage Inventory & Facility Profile

2. Regulatory Applicability & Plan Tier

Tier I Qualified Facility
Aggregate Aboveground Capacity: 6,550 Gallons
1,320-Gallon SPCC Threshold: EXCEEDED (Plan Required)
Facility Classification Tier: TIER I QUALIFIED FACILITY
Professional Engineer (PE) Certification: NOT REQUIRED (Self-Certified)
EPA Streamlined Template (Appendix G): Eligible for Appendix G Template
Maximum Civil Penalty: Up to $59,973 / Day
Tier I Qualified: Capacity is between 1,320 and 10,000 gallons, with no single container >5,000 gallons and no disqualifying spill history. Facility may self-certify using EPA Appendix G template without hiring a PE.
Secondary Containment: 40 CFR § 112.7(c) requires appropriate secondary containment (dikes, berms, catchment basins) for all bulk storage containers.

EPA Clean Water Act SPCC (40 CFR Part 112) FAQs

What is the applicability threshold for an EPA SPCC Plan under 40 CFR Part 112?

Under 40 CFR § 112.1, a facility must prepare an SPCC plan if: (1) it has an aggregate aboveground oil storage capacity exceeding 1,320 U.S. gallons (counting only containers with a capacity of 55 gallons or greater), OR completely buried underground storage exceeding 42,000 gallons; and (2) due to its location, there is a reasonable expectation of an oil discharge reaching navigable waters.

What containers are counted toward the 1,320-gallon SPCC threshold?

Under 40 CFR § 112.1(d)(2), only containers with a shell capacity of fifty-five (55) U.S. gallons or greater are counted. Containers under 55 gallons (e.g., 5-gallon pails, small lube cans) are completely exempt from the capacity calculation.

What is the difference between a Tier I and Tier II Qualified Facility?

A Tier I Qualified Facility has total aboveground storage capacity of 10,000 gallons or less, with no individual aboveground container exceeding 5,000 gallons; it may self-certify its SPCC plan using the streamlined EPA template (Appendix G). A Tier II Qualified Facility also has ≤10,000 gallons but has at least one container >5,000 gallons; it can self-certify a non-template plan without a Professional Engineer (PE).

When is a Professional Engineer (PE) certification required for an SPCC Plan?

A facility with aggregate aboveground storage capacity exceeding 10,000 gallons, or any facility that experienced a single discharge of oil >1,000 gallons or two discharges >42 gallons in a 12-month period, MUST have its SPCC plan reviewed and certified by a licensed Professional Engineer.