EPA SPCC Tier I & Tier II Qualified Facility Auditor (40 CFR Part 112)
Calculate aggregate aboveground oil storage capacity, determine SPCC applicability (1,320-gallon threshold), and audit eligibility for Tier I / Tier II self-certified plans under 40 CFR § 112.3.
Statutory Guidance & FAQs
A facility is subject to SPCC rule requirements if it has an aggregate aboveground oil storage capacity greater than 1,320 U.S. gallons (counting only containers of 55 gallons or greater), or a completely buried storage capacity greater than 42,000 gallons, AND could reasonably be expected to discharge oil into navigable waters or adjoining shorelines.
To be a Qualified Facility under 40 CFR § 112.3(g), the facility must have 10,000 gallons or less in aggregate aboveground capacity and have had no single discharge >1,000 gallons or two discharges >42 gallons in the past 3 years. If no individual aboveground container exceeds 5,000 gallons, it qualifies for Tier I (EPA self-certification template without Professional Engineer stamp).