🛢️ Clean Water Act § 311 Oil Pollution SPCC Plan & Facility Response Plan Auditor

Audit EPA Spill Prevention, Control, and Countermeasure (SPCC) regulations under Clean Water Act Section 311 and 40 CFR Part 112: 1,320-gallon aboveground storage capacity threshold, secondary containment engineering requirements, Tier I / Tier II Qualified Facility self-certification vs PE certification, and Facility Response Plan (FRP) substantial harm criteria.

SPCC & FRP Regulatory Parameters

Gallons
Count containers ≥ 55 gallons. Threshold is 1,320 gallons.
Gallons

40 CFR Part 112 Audit Verdict

SPCC Plan Required: Tier II Qualified Facility
  • 1,320-Gallon SPCC Threshold: Exceeded (8,500 gal ≥ 1,320 gal)
  • Applicable SPCC Facility Tier: Tier II Qualified Facility
  • PE Certification Mandate: Self-Certification Allowed
  • Secondary Containment Compliance: Compliant (110% Capacity)
  • Facility Response Plan (FRP): Not Required (< 1M Gallons)
40 CFR § 112.3 Qualified Facility Rules

Under 40 CFR Part 112: (1) Tier I Qualified Facility: Total aboveground capacity ≤ 10,000 gallons, no individual container > 5,000 gallons, clean spill history; can use EPA's streamlined template without PE certification. (2) Tier II: Capacity ≤ 10,000 gallons but has an individual tank > 5,000 gallons; self-certification allowed with full plan format. (3) Non-Qualified Facility: Capacity > 10,000 gallons; mandatory Professional Engineer review and certification.