NEC Article 220 Residential Electrical Load Calculator

Calculate residential electrical service demand loads under National Electrical Code (NEC) Article 220, determine total calculated amperage, and size 100A, 200A, or 400A service panels.

1. Home Square Footage & Small Appliance Circuits

NEC 220.12: General lighting at 3 Volt-Amperes (VA) per square foot
NEC 220.52(A) requires a minimum of 2 circuits at 1,500 VA each

2. Major Fixed Electric Appliances (Nameplate VA)

NEC Table 220.55: Demand factor calculation
NEC 220.54: Minimum 5,000 VA

Calculation & Documentation Summary

Enter parameters above and click calculate or generate to view full results.

🏠 Home Hub

National Electrical Code (NEC Article 220) Load Calculation

Electrical inspectors require a formal NEC Article 220 Residential Load Calculation before issuing electrical permits for main service panel upgrades (such as upgrading from an obsolete 100-Amp fuse box to a modern 200-Amp breaker panel).

Step-by-Step Standard Method

  1. General Lighting Load: 3 VA per square foot of habitable living area (NEC 220.12).
  2. Small Appliance & Laundry Circuits: 1,500 VA for each kitchen small appliance circuit (minimum 2) and 1,500 VA for the laundry branch circuit (NEC 220.52).
  3. General Demand Factor: The first 3,000 VA is rated at 100%, and the remainder is rated at 35% (NEC Table 220.42).
  4. Appliance Demand Factors: Electric ranges are factored under NEC Table 220.55 (typically 8 kW demand for standard household ranges), and the largest heating or cooling load is included at 100% under non-coincident load rules (NEC 220.60).