Off-Grid Solar Inverter & Surge Capacity Sizing Calculator

Size off-grid and hybrid solar inverters (continuous kW & peak motor surge), calculate battery bank DC current draw, and determine recommended copper cable gauge.

1. Continuous AC Electrical Loads

Lighting, electronics, refrigerator, fans, computers running simultaneously
e.g. Submersible well pump (1.5 HP = ~1,800W) or Central AC compressor

2. DC Battery Bus Architecture

Calculation & Documentation Summary

Enter parameters above and click calculate or generate to view full results.

🏠 Home Hub

Engineering Calculations for Off-Grid Inverter Sizing

An off-grid solar inverter must satisfy two independent power thresholds: continuous running power (measured in continuous Watts/kVA) and instantaneous inductive motor surge capacity (often 3x to 5x running wattage for well pumps, air compressors, and refrigeration equipment).

Why 48-Volt DC Architecture is Standard

Under Ohm's Law (Amps = Watts ÷ Volts), powering a 5,000-Watt load on a 12V battery bank requires over 450 Amps of continuous DC current, demanding massive 4/0 copper cables and generating extreme heat. By stepping up to a 48V DC bus, current drops to ~110 Amps, greatly improving system safety, efficiency, and inverter lifespan.