NEC Requirements for US Residential EV Charger Installation
Installing a dedicated 240-volt Level 2 electric vehicle supply equipment (EVSE) station requires compliance with National Electrical Code (NEC) Article 625. Because an EV charger operates continuously for multiple hours, NEC mandates that it be treated as a continuous load, requiring conductors and overcurrent protection to be sized at 125% of the charger's rated amperage.
- 40-Amp Charging (9.6 kW): Requires a dedicated 50-Amp dual-pole circuit breaker and #6 AWG NM-B copper Romex (or #8 AWG THHN in conduit).
- 48-Amp Charging (11.5 kW): Requires a hardwired connection with a 60-Amp breaker and #6 AWG copper wire rated at 75°C.
- GFCI Breaker Requirements: NEC 2020 / 2023 requires all 240V receptacles (NEMA 14-50) installed in garages and outdoors to feature GFCI breaker protection.