Calculation & Generation Results
About This Tool
Calculate dedicated 240V circuit breaker size (80% continuous load rule), copper wire gauge (THHN vs Romex NM-B), and conduit sizing under NEC Article 625 for Tesla, ChargePoint, and universal Level 2 EV charging stations.
Frequently Asked Questions
What does the NEC continuous duty 125% rule mean for EV chargers?
Under National Electrical Code (NEC) Article 625.41, EV charging is defined as a continuous load (drawing maximum current for 3 hours or longer). Electrical breakers can only be loaded continuously to 80% of their rating. Therefore, a 48-amp charger requires a 60-amp breaker (48A × 1.25 = 60A), and a 40-amp charger requires a 50-amp breaker.
Can you run 48-amp EV charging through a NEMA 14-50 outlet?
No. The maximum continuous charging rate permitted through a standard NEMA 14-50 receptacle on a 50A breaker is 40 amps (80% of 50A). To charge at 48 amps (11.5 kW), the charger MUST be permanently hardwired directly to a dedicated 60A circuit.