CTI / ASHRAE 90.1

Cooling Tower Cycles of Concentration & Makeup Calculator

Calculate cooling tower evaporation, blowdown, drift, makeup water requirement, cycles of concentration (CoC), and annual utility cost savings.

Cooling Tower Operating Parameters
Hydraulic & Water Conservation Results
Annual Water Cost Savings (Optimized)
--
--
Total Makeup Water Rate (Current)
--
--
Evaporation Rate (E)
--
--
Blowdown Rate (B)
--
--

Cooling Technology Institute (CTI) Equations:

  • Evaporation: E = GPM × ΔT × 0.0008 (or ~3.0 GPM per 100 tons at 10°F range).
  • Blowdown: B = E / (CoC - 1). Increasing CoC from 3 to 6 reduces blowdown volume by over 60%.
  • Makeup Water: M = E + B + Drift (drift is capped at 0.005% of recirculation flow).
🏠 Home Hub