ASHRAE Fundamentals

Cooling Coil Sensible / Latent & Condensate Flow Calculator

Calculate HVAC cooling coil sensible and latent thermal loads (tons), Sensible Heat Ratio (SHR), and hourly moisture condensate drain flow (GPH) per ASHRAE psychrometrics.

Airflow & Psychrometric Conditions
Coil Capacity & Condensate Rate
Condensate Water Drain Flow
--
--
Total Cooling Capacity
--
--
Sensible Cooling Capacity
--
--
Latent Dehumidification Load
--
--

ASHRAE Psychrometric Coil Equations:

  • Sensible Heat: q_s = 1.08 × CFM × ΔT_db (Btu/hr).
  • Latent Heat: q_L = 4,840 × CFM × ΔW (Btu/hr).
  • Condensate Water (GPH) = (CFM × 60 × ΔW) / (7,000 grains/lb × 8.34 lbs/gal).