NFPA 291 / AWWA M31
Water Main Fire Flow & Residual Pressure Calculator
Calculate available municipal fire flow at 20 psi residual pressure using Hazen-Williams rating curves and NFPA 291 hydrant color classifications.
Hydrant Flow Test Data (Field Pitot Test)
Flow Capacity & NFPA 291 Class
Available Flow at 20 psi (Q20)
--
--
NFPA 291 Hydrant Class & Color
--
--
Pressure Drop During Test (ΔP)
--
--
ISO Required Fire Flow Verdict
--
--
NFPA 291 Hydrant Color Coding Standards:
- Formula: Q_20 = Q_test × [ (P_static - 20) / (P_static - P_residual) ]^0.54.
- Class AA (Light Blue): 1,500 GPM or greater.
- Class A (Green): 1,000 to 1,499 GPM | Class B (Orange): 500 to 999 GPM | Class C (Red): Below 500 GPM.