Commercial Kitchen Ventilation Code Standards
- IMC Table 507.2.2 Minimum CFM Rates: Wall-mounted canopies require 200 CFM/ft (Light), 300 CFM/ft (Medium), 400 CFM/ft (Heavy), and 550 CFM/ft (Extra Heavy). Island hoods require 30% to 50% higher airflows due to the absence of rear backsplashes.
- NFPA 96 Duct Velocity: Grease exhaust duct systems must maintain air velocity between 1,500 FPM and 2,500 FPM. Lower velocities cause grease vapor to condense into liquid grease; higher velocities cause severe acoustic rumble.
- Make-Up Air (MUA) Balancing: Introducing 80% to 90% tempered make-up air prevents negative building pressure that would otherwise cause doors to slam shut and backdraft gas water heaters.