UPC Chapter 10 / ASME
Commercial Kitchen Grease Interceptor Sizing Calculator
Size commercial restaurant hydromechanical grease interceptors (HGI) and outdoor gravity grease interceptors (GGI) per Uniform Plumbing Code (UPC) formulas.
Kitchen Plumbing Fixtures & Flow
Interceptor Capacity & Pumping Schedule
Recommended Minimum Rating
--
--
Grease Storage Capacity
--
ASME A112.14.3 Tested Minimum
Calculated Peak Drainage Flow
--
--
Cleanout Pumping Frequency
--
Based on 25% Rule (UPC 1014.3.4)
Uniform Plumbing Code (UPC Table 1014.2.1):
- HGI rated flow (GPM) must equal or exceed 75% of connected fixture drainage volume emptied in 1.5 minutes.
- Hydromechanical units must retain a minimum of 2 pounds of grease per 1 GPM flow rating.
- Gravity interceptors must provide minimum 30-minute hydraulic retention time with 2-hour settling.