Plumbing Vent Pipe & DFU Calculator
Size dry vents, vent stacks, and relief vents. Verifies minimum vent pipe diameter and maximum allowable developed length based on Drainage Fixture Units (DFU) under IPC Table 906.1 and UPC Table 703.2.
Fixture Load & Vent Specifications
E.g., Bathroom group = 5-6 DFU, Kitchen sink = 2 DFU, Water closet = 3-4 DFU.
Maximum Allowed Developed Vent Length
120 Feet
PASS: 2" Vent supports up to 24 DFU across 120 ft developed length
Minimum Allowed Vent:
1-1/2" Min (1/2 Drain Size)
Roof Penetration Terminal:
3" Diameter (Frost Expansion)
Max Permissible DFU on 2":
32 DFU Maximum
Code Determination:
COMPLIANT
IPC Section 906 Compliant: A 2-inch vent serving 24 DFU on a 3-inch stack provides up to 120 feet of maximum developed length.
Plumbing Code Rules:
• 1/2 Diameter Rule: The diameter of an individual vent or vent stack shall be not less than one-half the diameter of the drain served, and never less than 1-1/4 inches.
• Frost Closure (IPC 903.2): Where frost or freezing occurs, each vent pipe through a roof shall be not less than 3 inches in diameter, increased at least 1 foot below the roof line inside the thermal envelope.