OmniCalc Hub NEC 2023 Article 450

Transformer OCPD & Conductor Calculator

Compute primary and secondary Full Load Amps (FLA), circuit breaker ratings, and 75°C copper wire gauges per NEC Table 450.3(B) and Table 310.16.

Transformer Specifications

NEC Overcurrent Protection (OCPD)
Primary Breaker
70 Amps
54.1 FLA @ 480V
Secondary Breaker
175 Amps
124.9 FLA @ 208V
Primary Min Copper Wire: #4 AWG THHN
Secondary Min Copper Wire: 2/0 AWG THHN
NEC Code Table: Table 450.3(B) < 1000V
Grounding Electrode: NEC 250.66 Table Sizing

NEC 450.3(B) Rules:

• FLA ≥ 9A: Primary only protection limited to 125% of FLA. If 125% does not correspond to a standard breaker, the next higher standard rating is permitted (Note 1).