Solar Rapid Shutdown (NEC 690.12) Calculator
Verify firefighter electrical safety compliance for rooftop photovoltaic systems under NFPA 70 NEC § 690.12. Evaluates array boundary zones, voltage attenuation, and initiation hardware.
PV System Architecture
NEC 690.12 Compliance Status
PASS: Fully Compliant
Within Array: ≤ 80V | Outside Array: ≤ 30V within 30 seconds
Boundary Dimension:
1.0 Ft from Array Edge
Inside Boundary Limit:
≤ 80 Volts (Module-Level)
Outside Boundary Limit:
≤ 30 Volts within 30 sec
Required Placard:
NEC 690.56(C) Yellow Plaque
Microinverter systems inherently satisfy NEC 690.12. When the AC breaker opens, microinverters stop pulsing within milliseconds, reducing rooftop DC to isolated 40V module voltage (<80V limit).
NEC § 690.12 Statutory Rules:
• Boundary Definition: The rapid shutdown boundary extends 1 foot (305 mm) from the array in all directions and 3 feet from point of entry into a building.
• Inside Array (NEC 2020/2023): Controlled conductors inside the boundary must be limited to ≤ 80 volts within 30 seconds of initiation.
• Outside Array: Controlled conductors outside boundary must drop to ≤ 30 volts and ≤ 240 VA within 30 seconds.