NEC 2023/2026 Table 220.56
NEC Table 220.56 Commercial Kitchen Electrical Feeder Demand Sizer
Size electrical service and feeder load demands for commercial kitchens (restaurants, cafeterias) using statutory demand factors (1-2 units: 100%, 3 units: 90%, 4 units: 80%, 5 units: 70%, 6+ units: 65%) with connected load comparisons under Article 220.56.
⚡ System Voltage & Electrical Service
NEC 220.56: Demands cannot be lower than sum of 2 largest loads.
🍳 Commercial Kitchen Equipment Load (kW)
Total Connected Load
92.5 kW
6 Cooking Units Connected
NEC 220.56 Demand Load
60.1 kW
65% Demand Factor Applied
Feeder Current Rating
167 Amps
Standard Breaker: 175A / 200A