HVAC Hydronic Expansion Tank Sizing Calculator (ASME Section VIII)
Size ASME Section VIII bladder and diaphragm hydronic expansion tanks for closed heating and chilled water loops: calculate thermal liquid expansion volumes, fill vs relief pressures, and required total tank capacity (gallons).
Boilers, chillers, coils, and piping
Static head height (ft / 2.31) + 5 PSI
Relief valve setting minus 10% safety margin
ASME Section VIII Expansion Tank Sizing
Thermal Expansion Volume (Ve):
88.5 Gallons
Pressure Acceptance Factor:
0.418
Recommended ASME Tank Capacity (Vt):
211.7 Gallons (Use 240 Gal Tank)
Tank Pre-Charge Pressure:
20.0 PSIG (Match P1)