OmniCalc Hub IMC Code

Commercial Kitchen Hood Exhaust CFM Calculator

Size restaurant Type I commercial kitchen ventilation. Computes minimum code exhaust airflow (CFM) under International Mechanical Code (IMC Table 507.2.1), 80%–90% make-up air supply, and NFPA 96 grease duct velocity.

Hood Style & Cooking Equipment

Ventilation Airflow & Duct Sizing

Min Exhaust Airflow
3,000 CFM
Make-Up Air Supply
2,550 CFM
Round Duct Diameter
18" Round
IMC 507.2.1 Code Multiplier: 300 CFM / linear ft
NFPA 96 Target Duct Velocity: 1,500 - 2,200 FPM (Feet Per Minute)
Equivalent Rectangular Duct: 16" × 16" Welded Steel