HVAC Cooling Tower Heat Rejection, Evaporation & Makeup Water Calculator
Calculate open cooling tower heat rejection (15,000 BTU/hr/ton), water evaporation rate GPM, cycles of concentration (COC), blowdown discharge, drift loss, and daily municipal makeup water demand.
1 Tower Ton = 15,000 BTU/hr heat rejection (3 GPM/ton)
Typically 3.0 GPM per nominal ton
Standard: 95°F entering, 85°F leaving (ΔT = 10°F)
Modern cellular drift eliminators ~0.005%
Cooling Tower Water Balance Summary
Evaporation Rate (E):
12.0 GPM
Blowdown / Bleed-Off Rate (B):
3.4 GPM
Total Makeup Water Demand (M):
15.5 GPM (Makeup Line: 1-1/2")
Daily Water Consumption:
14,880 Gallons / Day