Calculate supply and exhaust airflows (CFM), minimum 12 Air Changes per Hour (ACH), exhaust offset differentials, and room pressurization (-0.01 in. w.c. AII vs +0.01 in. w.c. PE) for hospital airborne isolation suites per ASHRAE 170.
Isolation Suite Room Type
Airborne Infection Isolation (AII) - Negative Pressure (-0.01" w.c.)
Protective Environment (PE / Immunocompromised) - Positive (+0.01" w.c.)
Anteroom Air Barrier / Buffer Zone
Room Floor Area (Sq Ft)
Ceiling Height (Feet)
Minimum Total Air Changes (ACH)
12 ACH (ASHRAE 170 New Construction Standard)
15 ACH (Enhanced Infection Control)
6 ACH (Legacy Existing Building Exemption)
Minimum Outdoor Air ACH
2 ACH Minimum Outdoor Air (ASHRAE 170 Table 7.1)
100% Dedicated Outdoor Air (DOAS - 12 ACH OA)
Door Leakage & Offset Design
100 CFM Offset (Standard tight gasketed door, ~0.5 sq ft crack)
150 CFM Offset (Standard unsealed undercut door)
75 CFM Offset (Drop seal pneumatic door)
Calculate Isolation Airflows
Reset