Standby Generator ATS Sizing Calculator
Size residential and commercial Automatic Transfer Switches (ATS). Determine continuous amp rating, Service Entrance (SE) rated disconnect requirements, and intelligent load-shedding modules under NEC ยง 702.
Electrical Service & Generator
Required ATS Specification
200 Amp SE-Rated
Service Entrance Rated with built-in utility main breaker
Generator Output Amps:
91.7 Amps (22 kW @ 240V)
Load-Shedding Modules:
2 A/C Lockout Modules Needed
Short Circuit Withstand:
10 kAIC Withstand Rating
Neutral & Ground Bonding:
Bonded in ATS (First Disconnect)
Whole-House Backup: Installing a 200A SE-rated ATS allows your 22 kW generator to power the entire main panel. Because generator output (91.7A) is less than the 200A utility service, NEC 702.4 requires installing 2 SACM/SMM load-shedding modules to lock out dual AC compressors during generator operation.
NEC Article 702 Sizing Rules:
• NEC 702.4(B)(2): The automatic transfer equipment must have a rating equal to or greater than the continuous full load of the equipment supplied (or the main utility panel rating in whole-house installations).
• Automatic Load Management: If generator capacity cannot support all connected loads, an energy management load-shedding system is legally mandatory.