Commercial Plumbing Domestic Water Pressure Booster Pump (ASPE) Calculator
Calculate commercial multi-story domestic water booster pump total dynamic head (TDH in PSI and feet), design flow demand (Hunter Curve GPM), suction city pressure, and motor horsepower (HP) per ASPE and UPC guidelines.
🚿 Building Elevation & Water Demand Inputs
Booster Pump Sizing & Motor Horsepower
Static Lift Head
36.8 PSI (85 ft)
Discharge Pressure Req.
101.8 PSI
Pump Pressure Boost (TDH)
66.8 PSI (154 ft)
Brake Horsepower (BHP)
7.2 BHP (10 HP Motor)
Recommended Pump Package
Duplex Booster System (2 x 65 GPM @ 154 ft TDH, 7.5 HP Each with VFD)