NFPA 96 / IMC 507 Kitchen Hood
Commercial Kitchen Type 1 Grease Exhaust Hood CFM & Makeup Air Calculator
Calculate required kitchen exhaust ventilation airflow (CFM) for commercial Type 1 grease hoods per IMC Section 507 and NFPA 96 based on cooking appliance thermal duty, hood overhang, duct velocity (1500 FPM), and makeup air.
๐ณ Hood Configuration & Cooking Appliance Classification
Required Exhaust Airflow
4,000 CFM
IMC Table 507.2.1 compliant
Dedicated Makeup Air
3,400 CFM
85% tempered supply
Grease Duct Sizing
20" x 19"
384 sq in @ 1,500 FPM
NFPA 96 Compliance
APPROVED
1200 - 2500 FPM window
Fire Protection & Engineering Construction Specifications
Grease Duct & Enclosure Mandates:
Duct Material: 16-gauge carbon steel or 18-gauge stainless steel (NFPA 96 ยง 5.1)
Construction: Continuous liquid-tight external weld seam
Slope Requirement: Min 1/4" per foot toward hood reservoir (< 75 ft run)
Shaft Clearance: 18" to combustibles (reduced with certified fire wrap)
Fire Suppression & Controls:
Fire System: UL 300 compliant wet chemical fire suppression system
Interlocks: Gas fuel supply and electric heat shutoff upon system trip
Exhaust Fan: Upblast centrifugal roof fan with hinged base & grease collector
Makeup Air Fan: Interlocked with exhaust fan to prevent negative draft