⚙️ OmniCalc Hub
ASHRAE / SMACNA Duct Sizing

Commercial HVAC Duct Static Pressure Drop & Equal Friction Sizer

Size commercial rectangular and round ductwork using the ASHRAE / SMACNA Equal Friction method (0.08 - 0.15 in. wg / 100 ft). Calculate hydraulic diameter, equivalent rectangular dimensions, velocity (FPM), and total external static pressure loss.

🌀 Airflow & Equal Friction Design Parameters

Round Duct Diameter
18.2 in
Exact circular equivalent
Sized Rectangular Duct
22" x 14"
Aspect ratio: 1.57
Air Velocity (FPM)
1,120 FPM
Comfort Zone (< 1500)
Total Static Loss (ESP)
0.20 in. wg
Across 200 total equiv ft

Duct Flow Characteristics & Fan Selection Guide

Duct Geometry Breakdown:

Equivalent Hydraulic Diameter: 17.2 in
Cross-Sectional Area: 2.14 sq ft (308 sq in)
Sheet Metal Perimeter (Girth): 72 inches (6.0 ft)
Estimated Sheet Metal Weight: 26-gauge galvanized (~280 lbs)

Aerodynamic Performance:

Velocity Pressure (Pv): 0.078 in. wg (V/4005)²
Friction Drop in Straight Run: 0.120 in. wg
Fitting Dynamic Pressure Loss: 0.080 in. wg
ASHRAE 90.1 Compliance: Velocity <= 1,500 FPM for branch ductwork