NFPA 13 Hydraulic Calculation
Commercial Fire Sprinkler Hydraulic Remote Area & Density (NFPA 13) Calculator
Determine NFPA 13 design remote area size, discharge density (GPM/sq ft), minimum sprinkler head flow & pressure (q = K*sqrt(P)), and total base-of-riser water supply demand including hose stream allowance.
🚒 Occupancy Hazard & Sprinkler Hydraulic Parameters
Design Remote Area
1,500 sq ft
12 operating heads
Min Single Head Flow (q)
26.0 GPM
Density × Coverage Area
End Head Min Pressure
21.6 psi
q = K * sqrt(P)
Total Base-of-Riser Demand
612 GPM
Includes 250 GPM hose
Hydraulic Demand Breakdown & Water Supply Summary
| Demand Component | Flow Rate (GPM) | Pressure Requirement (psi) | NFPA 13 Standard Reference |
|---|